The 9095X is a top-fill overfill prevention valve designed to prevent overfilling storage tanks by providing a positive shut-off during a pressurized fill.

For use on clean liquids only.

Standard Features

Fill adaptor and shut-off mechanism are factory-assembled for ease of field installation

Straight female threaded adaptor facilitates valve installation to a precise set point

Minimum shut-off height is 1” from the tank top

Full flow to shut-off point, cushioned closure eliminates shock

Drop tube adaptor accepts 2” drop fill tubes (Morrison 419)

Integral pressure relief

Integral anti-siphon function

305C—2000 cap included with 1100 and 2200 models

Data Sheet

Download

 

Product Features

Standard Features

Fill adaptor and shut-off mechanism are factory-assembled for ease of field installation

Straight female threaded adaptor facilitates valve installation to a precise set point

Minimum shut-off height is 1” from the tank top

Full flow to shut-off point, cushioned closure eliminates shock

Drop tube adaptor accepts 2” drop fill tubes (Morrison 419)

Integral pressure relief

Integral anti-siphon function

305C—2000 cap included with 1100 and 2200 models

 

Mechanical Test Mechanism

Verify the operation of the valve by activating the test mechanism at any time during the filling process

Available on all models

 

Construction Details

  • Direct fill adaptor: Passivated aluminum
  • Remote fill adaptor: Powder coated ductile iron & stainless steel
  • Shaft, linkage, and hardware: Sstainless steel
  • Lower pipe nipple: E-coated steel
  • Body: Passivated aluminum
  • Drop tube adaptor: Passivated aluminum

 

Operational Criteria

Minimum 5 PSI flow requirements

Maximum operating pressure is 100 PSI

Maximum viscosity of 300 centistokes

A tight fill connection is required for the valve to operate

The estimated flow rate is 230 GPM at 10 PSI pressure drop

 

Code Compliance

ULC-S661-10 listed, NFPA 30, 30A, UFC, IFC, PEI/RP 200, PEI/RP 600, Florida DEP EQ-858, and California EVR models available

Product Ordering Instructions

 

 

Figure Suffix Size Tank Opening Drop Tube Application
9095X

 

1100 AV 2” 4” No Generator base tanks with integrated spill container, Direct Fill
9095X

 

6100 AV 2” 4” No Generator base tanks with integrated spill container, Remote Fill
9095X

 

2200 AV 2” 4” Yes Low profile tanks; integrated spill container, Direct Fill
9095X

 

6200AVEVR 2” 4” Yes Valve with female threaded top connection, Remote Fill, EVR approved
9095X

 

2800 AV 2” 4” Yes General purpose and aviation, Direct Fill
9095X

 

6800AVEVR 2” 4” Yes General purpose and aviation, Remote Fill, EVR approved
9095ATM

 

1000 AK Mechanical test mechanism kit for 9095X